A normal timer instruction specifies the effective timer range in the unit used on the POU. Since the timer numbers (T0 to T8191) are treated as a local devi... Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
Yes, you can. On the 'Load from PLC' dialog, check 'Reflect Real Structure,' and then connect the PLC online. If this option is checked, the loader internall... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
To make the 'Use USB port' check box selectable, the USB driver for MICREX-SX must be installed on the PC in use. Install the USB driver (dedicated) conta... Show Detail
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req... Show Detail