You can use the following program as an alternative. When you turn on the differential command 'M0,' the differential output 'M2' turns ON for one scan. ... Show Detail
The text color of I/O addresses (X, Y) is red. You cannot change it. Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
The SPH3000 series has 'high-speed program (high-speed PG) memory' area in the program memory. When you store a POU in this area, the POU execution speed be... Show Detail
To use the failure diagnosis function, you need to install '.NetFramework' on your computer. '.NET Framework2.0' is contained in the product CD. If your OS... Show Detail
Check the following system memory. If %MX10.4.5 (SM45) 'I/O module error' is turned on, removal of a module may be the cause of the nonfatal fault. [Relat... Show Detail
The addresses of structure data are automatically assigned by the D300win to ensure optimum memory assignment. Data sampling is a method to acquire a certai... Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
The measurement accuracy does not include zero junction compensation accuracy. The zero junction compensation accuracy is ±1°C (at ambient temperature 0°C ... Show Detail
61-70 of Total 398