What is the difference between the LG and FG terminals of the power supply module (Type_ NP1S-22)?
The LG terminal is a line filter ground terminal in the power supply module. It is intended for guiding any external noise produced in the power supply or sw... Show Detail
Usually, set the CPU No. to 0. The CPU No. 0 works as a master of an SX bus system. In a multi-CPU system or a CPU redundant system which uses multiple CPU ... Show Detail
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this... Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
You can mount or remove a CPU module during system operation, but not a power supply module. [Related document] For the details of hot plugging function, r... Show Detail
When you use battery-less operation on the SPH, is the history of RAS information recorded?
During battery-less operation, previous fault information and other 'history of RAS' are not saved. Only the present RAS information is displayed. Show Detail
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of... Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
(1) With the SPH300/2000 Series, it is used to back up the data memory of the retained attributes, calendar IC memory, and RAS information. (2) With the SPH2... Show Detail
1-10 of Total 34