When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow. Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
Both the pulse output and control output are open collector outputs. They should be used within the following ranges (1) Pulse output_ 30 V DC, 40 mA or less... Show Detail
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
You can refer to sample project Mptpf4.zwt stored in the ZIPPED folder in the D300win folder. Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
I cannot register a dummy module (Type_ NP1F-DMY) with the system definitions using the loader.
The purpose of a dummy module is to use it as a temporary replacement of an I/O module that has been defined with the system but does not actually exist for ... Show Detail
1-10 of Total 50