In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
Note the following points (1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected. (2) The Z-phase/timing input signal f... Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft... Show Detail
When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
Pulse input type_ A-phase for the pulse and B-phase for the sign. Show Detail
What measures can I take against external noise of the high-speed counter (Type_ NP1F-HC2)?
Use the recommended shielded twisted pair cable mentioned in the User's Manual. Also provide shielding. Show Detail