Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
What is the difference between RS-485 and RS-422 ?
RS-485 is upper compatible with RS-422. In general, RS-422 devices mainly use 4-wire connection method, while RS-485 devices mainly use 2-wire connection met... Show Detail
R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5). Show Detail
You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
The number of M_OPEN FBs that can be opened simultaneously is limited to 56. The number of FBs that can be simultaneously opened for each module depends on t... Show Detail
Set the port No. as described below. (1) For NP1L-RS2_ Set '0.' (2) For NP1L-RS4_ Set '1.' See the figure below for the setting for each type of genera... Show Detail
Does an RS-485 communication module (Type_ NP1L-RS1/RS4/RS5, etc.) support the MODBUS procedure?
The SX-Programmer Expert supports MODBUS communication (master function) using an FB. Communication with a MODBUS slave device is possible by using SPH_CP... Show Detail
Does the general-purpose communication module support the BSC procedure?
No, it doesn't. Show Detail
Yes, it is possible. Of the parameter setting items of initialization, changes made to specific parameter items (such as frame detection, code conversion and... Show Detail
1-10 of Total 53