You don't need a dedicated cable. Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software. Show Detail
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro... Show Detail
Yes, it is possible. Of the parameter setting items of initialization, changes made to specific parameter items (such as frame detection, code conversion and... Show Detail
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode. Various loader commands have been... Show Detail
A 'client' is a device that collects data. Since the PLC is a device from which data is collected, there is no OPC client. Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Does an RS-485 communication module (Type_ NP1L-RS1/RS4/RS5, etc.) support the MODBUS procedure?
The SX-Programmer Expert supports MODBUS communication (master function) using an FB. Communication with a MODBUS slave device is possible by using SPH_CP... Show Detail
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory. Without handshaking, it is not... Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
It enables reception only when CD (Carrier Detection) is ON. (Other operations are the same as those in the DTE mode.) Show Detail
1-10 of Total 53