Yes, it is the same. Show Detail
It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
One M_OPEN consumes one port of SPORT_NO, which is the local port. RPORT_NO is the port of the other end of the communication seen from the SX. Show Detail
What is necessary for MODBUS_TCP communication between SPH and an external device?
The following are necessary. 1) Hardware Ethernet interface module (NP1L-ET1) or CPU module with built-in Ethernet (SPH2000/3000 series CPU types w... Show Detail
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB. After writing, the power (or reset) o... Show Detail
The SX does not allow the use of a single SPORT_NO (range_ 1 to 127) for multiple connections simultaneously. When you want to connect multiple ports, use a ... Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
1-10 of Total 25