Selecting the DCE mode for the communication parameter_ DCE designation keeps DSR always on. Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
Is it possible to use the optical converter NP1L-OL1 between processors as with the P-link?
The optical converter NP1L-OL1 is an optical converter of the SX bus. It cannot be used because the SX bus is not a link between processors. Show Detail
No, it cannot be used as it is. It requires resources to be added, the system configuration definitions to be changed, I/O groups to be reset and other ta... Show Detail
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.) The rated current is 40 mA and an encoder that permits t... Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
Is it possible to indirectly specify the timer set value with the Standard Loader (Type_ NP4H-SWN)?
Yes, it is possible. Input a memory address (DLxx) instead of an immediate value as the operand of the timer instruction. Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail
51-60 of Total 398