In MICREX-SX, a scan list is automatically created by registering the remote I/O to be connected to the master module in the system configuration definitions... Show Detail
When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi... Show Detail
There is a limit to the number of POUs that can be opened simultaneously_ 31 including 'Data 1,' 'Simulation' and 'AFB.' Show Detail
No, it cannot be used as it is. It requires resources to be added, the system configuration definitions to be changed, I/O groups to be reset and other ta... Show Detail
Can a master control instruction be used in the MICREX-SX Series?
(1) For Expert (D300win) No master control instruction is provided. This is because the MICREX-SX Series is dedicated to programmable logic controlle... Show Detail
Up to 127 levels of nesting is possible. Show Detail
The area is cleared when the power supply is turned off once and turned on again. The P/PE link memory is located in the built-in memory (RAM) of the P/PE-l... Show Detail
How can I use the present value of the timer (TON) with the Standard Loader (Type_ NP4H-SWN)?
You can set the present timer value by specifying the operand with identifier T. Example_ |--| |--[ MOVE T0 ? DM10 ]--| Show Detail
Can I use a router for FL-net?
You cannot use a router because FL-net does not support the use of subnet. *Related document: For the notes on using FL-net, refer to 'Appendix 2-8 Differen... Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail