Is it possible to use the loader connection cable NP4H-CB2 in combination with a converter provided by BLACK BOX?
NP4H-CB2 cannot be combined with a BLACK BOX converter for use.
Use NP4H-CB2 in combination with a converter NW0H-CNV (for RS-232C) or NP4H-CVU (for USB).
Show Detail
- No:1372
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:43
- Category:
Accessory
-
In a redundant system, what will happen to the P-link memory at the time of switchover to a standby CPU?
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb...
Show Detail
- No:1343
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
With the Standard Loader (Type_ NP4H-SWN) version 2, colors can be specified for local timers and counters. How can I color them in print?
The Standard Loader does not support color printing.
Show Detail
-
With the general-purpose communication module (Type_ NP1L-RS□), in what cases does 'C0_ Hardware error detected during receiving' occur?
It occurs when any of the overrun, parity and framing errors is detected in the serial port of a general-purpose communication module.
Show Detail
-
How does the redundant system handle tasks being executed when the operation is switched from an operating CPU to a standby CPU?
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task.
Show Detail
- No:1530
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I use the hot plug base board with station No. setup function (Type_NP1BS-13D). When I remove a module, how can I identify the removed module in D3...
Check the following system memory.
(1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67)
(2) Configuration fault information %MW10.68 to %MW1...
Show Detail
- No:1482
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Is it possible to use a variable for the initial value, end value and incremental value by using a 'FOR statement' of the ST language?
Yes, it is possible. Note, however, that the values are of the INT data type.
Show Detail
- No:1337
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
Do you have longer expansion cables for connecting an expansion unit to a main unit in the SPF series?
No, the expansion cable supplied with the expansion unit is only available.
Show Detail
- No:1487
- Displayed Date:2023/04/25 19:00
- Category:
Others
-
Do I have to connect T-link devices (slave stations) connected to T-link in ascending order of address?
No, you do not have to connect T-link devices in ascending order of address.
In addition, you can assign addresses at some intervals for the future expans...
Show Detail
-
1) When converting a program on Standard, about 100 FBs are registered in 'Function Blocks.' Are they all FBs being used? 2) Can I find out where a...
1) By the mechanism of program conversion, unused FBs are also registered.
However, FBs not used in the program are not downloaded to the CPU, therefor...
Show Detail