This is because when a compilation process is carried out, automatically assigned variables (variables for which AT specification is not used) and FB instanc... Show Detail
Is it possible to use the optical converter NP1L-OL1 between processors as with the P-link?
The optical converter NP1L-OL1 is an optical converter of the SX bus. It cannot be used because the SX bus is not a link between processors. Show Detail
While 'DTR_ terminal ready' can be used with RS-232C, this control line is not present for RS-485. If no response is received while data are exchanged, re... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
The temperature measurement value of the resistance temperature sensor (PT input) is unstable.
If this is caused by a fluctuation in the input temperature, moving average processing shown below may improve the condition. 1) Change the digital filter v... Show Detail
Pulse output completion is indicated by the 'Command pulse zero' signal. Normally, it is '1' to indicate the status of completion. When the number of pulses... Show Detail
None of them (NP1L-FL1, FL2 or FL3) can be used with general-purpose Ethernet communication. SX series FL-net modules comply with the following standards. ... Show Detail
The area is cleared when the power supply is turned off once and turned on again. The P/PE link memory is located in the built-in memory (RAM) of the P/PE-l... Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
It takes place only when data are received from an external device. Show Detail