The product type without 'RI' judges ON/OFF of the inputs by current. On the other hand, the product type with 'RI' judges ON/OFF of the inputs by voltage. ... Show Detail
With the SPH Series, the memory boundaries between the non-retain, retain, system FB and user FB memory areas can be changed to change the size of the respec... Show Detail
Yes, it is the same as in the SPH series (except for SPH3000MM). Show Detail
There is a difference between 'Unpassive' and 'Fullpasisve' as follows. 1) Unpassive: Communicates with a device that has any IP or port No. 2) Fullpassi... Show Detail
After changing the range with the rotary switch, turn off the power once and then turn it on again, and the software offset setting will be disabled. Show Detail
What is necessary for MODBUS_TCP communication between SPH and an external device?
The following are necessary. 1) Hardware Ethernet interface module (NP1L-ET1) or CPU module with built-in Ethernet (SPH2000/3000 series CPU types w... Show Detail
A nonfatal fault of the takt cycle monitoring error has occurred. What is a possible cause?
The takt cycle monitoring error is caused by the following factors_ (1) The preset takt cycle value specified in the system definition is shorter than the ac... Show Detail
You can display the mismatch circuit in the program and differences using the 'Compare Projects' command of the Expert loader. For the operating procedure, ... Show Detail
Check that the terminating plug is attached. Check also that the SX bus expansion cable is not broken. You need to attach an SX bus terminating plug at bot... Show Detail
Where is the USB driver of USB/RS-422 converter for personal computer loader (Type_NP4H-CVU)?
The USB driver of USB/RS-422 converter for personal computer loader is stored in the 'UsbToSerial' folder in the 'Driver' folder in the folder where the pers... Show Detail