Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
When the program for the MICREX-F is converted and opened, all user FBs in the library for the MICREX-F are automatically imported and contained in these fol... Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
How can I create a double-word counter with the Standard Loader (Type_ NP4H-SWN)?
Use an add instruction with the double-word operand to increment by 1 (+1). Show Detail
It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail