R_STS = 1 means 'send buffer overflow' detected by the general-purpose communication module. Check the communication format, communication interval and other... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
The IP address and port standard No. of the self station of the Ethernet module are stored in the internal ROM of the Ethernet module. After replacing an Eth... Show Detail
This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
Does data monitoring of the I/O area require the module to be registered in the system definition?
Unless you register the module in the system definition and set the I/O group in the CPU parameters, data monitoring is disabled because no memory is reserve... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Pulse output completion is indicated by the 'Command pulse zero' signal. Normally, it is '1' to indicate the status of completion. When the number of pulses... Show Detail
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail