How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
The multiplication of the high-speed counter module is automatically set as follows depending on the input pulse form_ ・ Forward pulse + Reverse pulse_ x1 ... Show Detail
When you enable optimization setting, compiling operation is changed to execute programs faster. Although different program codes are created, program execu... Show Detail
Yes, the SX series has a memory called 'system memory' to which flags indicating system operation statuses and fault statuses are assigned. Examples of the... Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
It takes place only when data are received from an external device. Show Detail
Can a master control instruction be used in the MICREX-SX Series?
(1) For Expert (D300win) No master control instruction is provided. This is because the MICREX-SX Series is dedicated to programmable logic controlle... Show Detail
Please describe the product SX communication middleware (Type_ NP4N-MDLW).
It is a local/remote data server (OPC server) compatible with Data Access (DA2.0) proposed by OPC (OLE for Process Control) extending OLE/COM for process con... Show Detail
If battery-less operation is enabled under the 'CPU running definition' setting, the content of the retain memory is not retained. Disable battery-less opera... Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail