When I output a variable worksheet of D300win to Excel, modify only comments on Excel and send it back to D300win, a compilation error is generated...
When the initial value of REAL type is '5.0,' for example, processing it through Excel changes it to '5' of the INT type and that causes a data type mismatch...
Show Detail
- No:1422
- Displayed Date:2023/04/25 19:00
- Category:
Error
-
In a redundant system, are the previous values retained for the SX bus and T-link outputs when the CPU is switched?
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.)
Show Detail
- No:1408
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
Is communication possible with the UI4 type not supported based on the manual description of the SX communication middleware (Type_ NP4N-MDLW)?
UI4 is not supported by the specification with the VB automation interface. Meanwhile, UI4 is supported by the custom interface specification.
Show Detail
- No:1381
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
Is it possible to count differential input pulses using a high-speed digital input module (Type_ NP1X3206-A)?
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.)
The rated current is 40 mA and an encoder that permits t...
Show Detail
- No:1373
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:43
- Category:
Function
-
I want to transfer data collectively. Is there any block transfer instruction equivalent to that of the MICREX-F Series? If not, how can I transfer...
The MOVE function can be used to transfer data of the same array data type.
You can also connect variables together without using MOVE.
Data of differe...
Show Detail
- No:1371
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:42
- Category:
Application
-
When I used the Standard Loader (Type_ NP4H-SWN) to input a timer instruction and specified the WM area for indirectly specifying the timer set val...
The set value of the timer must be a 32-bit (double-word) value. Specify DM (double-word), not WM (single-word). The memory to use may be DX or DL, as well a...
Show Detail
-
With D300win V2, I created global variables first and edited a ladder but some variables do not appear on the pull-down list for variable name inpu...
One likely cause is that any of the following characters is used in the variable worksheet
(1) A double-byte space is used. Use a single-byte space or tab...
Show Detail
-
What is the difference in the open-collector pulse input between the high-speed counter (Type_ NP1F-HC2) and the multi-channel counter (Type_ NP1F-...
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req...
Show Detail
- No:1341
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
An existing P-link system is composed of MICREX-F. If part of it is replaced with P-link of MICREX-SX, does the existing MICREX-F program need to b...
The existing MICREX-F program does not need any modification.
Show Detail
-
With a positioning control module (Type_ NP1F-MP2/MA2), what are the statuses of the status information signals after power-up?
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1].
The interrupt input sig...
Show Detail
- No:1318
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:17
- Category:
Function