It is not provided as internal memory. You need to create the circuit shown in the attached diagram. The example shows a circuit in which M0 repeats ON and O... Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
Yes, you can. Based on the rules of the IEC standard, you can omit 'X' in %MX, %IX, %QX and so on as long as they are BOOL type variables. Show Detail
The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Can I use both P-link and PE-link in one system?
No, you cannot. Show Detail
The error occurs because the address display mode is set to 'FLEX-PC,' but the address representation of the word device is not hexadecimal. For the addres... Show Detail
No, the expansion cable supplied with the expansion unit is only available. Show Detail
Is the programming support tool for MICREX-F series (MICREX-F PLC Programmer) still available?
Yes, it is. Ordering code: NP4H-SWN (The loader software for MICREX-F is included in the product CD together with the loader software for MICREX-SX.) Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
When the initial value of REAL type is '5.0,' for example, processing it through Excel changes it to '5' of the INT type and that causes a data type mismatch... Show Detail