Once a compilation error occurs during patch POU, the project must be compiled and downloaded again. Therefore, you need to stop the CPU. Please consider the... Show Detail
What is the meaning of EN and ENO of functions in Expert (D300win)?
The EN and ENO terminals of functions mean the start operation terminal and the operation result terminal, respectively. ・When the variable connected to the... Show Detail
This is because the SX bus loop-back plug is not connected. Connect a loop-back plug to the base board. Show Detail
When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow. Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail
No, you cannot access the input (output) parameter (WV*, DV*) for which the data length is set in words/ double-words by using a bit address within the user ... Show Detail
You cannot upgrade 'MICREX-F PLC Programmer' free of change. 'MICREX-F PLC Programmer' that can be installed as NL4N-WNSB is currently included with the p... Show Detail
In the system definition, group-type slave stations in any I/O configuration are registered as 'DeviceNet capsule.' In addition, the numbers of input and out... Show Detail
Can I upload a definition file downloaded from a configurator to NP1L-PD1/PD2?
No, you cannot upload a definition file. So, it is very important to keep backup of Definition file on PC side. Show Detail
I bought a USB 3.0 cable (A-B type) to connect to FLT-ASFKA. However, I cannot connect them.
FLT-ASFKA is equipped with a USB2.0 (B type) connector. The connecter shape is different between USB 3.0 (B type) and a USB 2.0 (B type). Purchase a USB 2.0 ... Show Detail
21-30 of Total 398