Yes, the SX series has a memory called 'system memory' to which flags indicating system operation statuses and fault statuses are assigned. Examples of the... Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
Yes, it is the same. Show Detail
I am using D300win to write a program. Is there any fixed data type for direct address variables?
Bit data are of the BOOL type, 16-bit data the WORD type and 32-bit data the DWORD type. Show Detail
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail
It may be caused by noise. Check the surrounding environment and wiring routes for any problem. The lowered communication speed is assumed to be because t... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
Common memory 1 and common memory 2 are handled together in terms of timing. However, to maintain the uniqueness of data including those in common memory 1 a... Show Detail