I am using the StandardV3 loader. Can I check the download history to the CPU?
When all the programs are downloaded into the CPU, the download history is not stored. However, when only a changed program is downloaded (online program c... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode. Various loader commands have been... Show Detail
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req... Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
The operation indication LED of an input module does not turn on by forcible ON/OFF. On the other hand, the operation indication LED of an output module tur... Show Detail
None of them (NP1L-FL1, FL2 or FL3) can be used with general-purpose Ethernet communication. SX series FL-net modules comply with the following standards. ... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
You can remove these warnings by deleting function blocks (FBs) that are not used in the program. Do either of the following methods: Method 1 1) After... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail