Instead of FNC120A-C10, can I use FNC130A-C10?
Yes, you can use FNC130A-C10 in combination with FNC120A-C10. Attach the same type of optical adapters at the both ends of the optical fiber. FNC130A has t... Show Detail
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing by, the changed program is loaded into both CPUs... Show Detail
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft... Show Detail
The 'SND' and 'RCV' LEDs on the P-link module (Type_ NP1L-PL1) look dark. Is this a fault?
The LEDs of the P-link module (Type_ NP1L-PL1) are designed to blink quickly in accordance with the ON/OFF of a signal. Although they look dim to the human e... Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
No, it does not support multicast transmission (sending/receiving). It does support broadcast transmission (sending/receiving). Show Detail
(1) With the SPH300/2000 Series, it is used to back up the data memory of the retained attributes, calendar IC memory, and RAS information. (2) With the SPH2... Show Detail