How can I display the list of device use status on Standard loaderV3
1) Double-click the 'Device' icon in the project view to open the device window. 2) Click the [Device Type] selection button (▼) and select a device the u... Show Detail
No, you cannot use NW0H-CNV. The RS-232C/422 converter for personal computer loaders (Type_NW0H-CNV) needs to be supplied power from the PLC side, however, t... Show Detail
(1) With the SPH300/2000 Series, it is used to back up the data memory of the retained attributes, calendar IC memory, and RAS information. (2) With the SPH2... Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
Version 2 is not based on the concept of online/offline switching. It is designed in such a way that you select online or offline when you open the screen. Show Detail
This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
Yes, you can. On the 'Load from PLC' dialog, check 'Reflect Real Structure,' and then connect the PLC online. If this option is checked, the loader internall... Show Detail
Is the backup battery consumed while the control power supply of the CPU is active?
The backup battery is intended to back up the data memory (SRAM) inside of the CPU. While the system is turned on, the power is supplied from the control pow... Show Detail
The product type without 'RI' judges ON/OFF of the inputs by current. On the other hand, the product type with 'RI' judges ON/OFF of the inputs by voltage. ... Show Detail
Timers (or other FBs such as counters) each have an internal memory that is called an instance. Therefore, after copying a timer, you need to define a vari... Show Detail