I use the hot plug base board with station No. Setup Function (Type_NP1BS-13D). When a module is removed, a nonfatal fault occurs. Please tell me h...
Check the following system memory.
If %MX10.4.5 (SM45) 'I/O module error' is turned on, removal of a module may be the cause of the nonfatal fault.
[Relat...
Show Detail
- No:1542
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
When I use the SX communication middleware (Type_ NP4N-MDLW) and specify (_) in the access path during the item registration for the client, Errno=...
Move to the item ID without using the access path on the client side (D_).
Show Detail
- No:1556
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
I have connected the SPH Series with the POD (UG Series) via the T-link. A code F8 is displayed on the screen of the POD. What is a possible cause?
This problem was probably caused by the following factors_
(1) Failed contact of the connector on the SPH,
(2) Failed contact on the POD (UG),
(3) Improp...
Show Detail
-
With the Standard Loader (Type_ NP4H-SWN) version 2, what does '*' displayed on the ladder bus indicate?
The '*' symbol on the ladder bus indicates a circuit being changed online.
It will disappear when you transfer the changed circuit to the PLC.
Show Detail
-
What is the rated current value of the fuse in the power supply module (NP1S-22)? I want to know to select the circuit breaker on the primary side ...
The rated current is 3 A.
Show Detail
- No:1641
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
Is there any simple way of delivering PLC operation data set with Excel to the PLC?
The SPH2000/3000 Series have a function of reading data in CSV file format to the memory in the CPU (CSV interface FB provided by Fuji Electric).
The data t...
Show Detail
- No:1295
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
When I uninstalled D300win, I only found BMP and JPEG data in C_D300winPAGELAYOUTSP081 and the all of the frame data included by default had been e...
This is because frame data with the template file names (default names) are deleted at the time of uninstallation. (Files created with new names are not dele...
Show Detail
-
With an Ethernet module (Type_ NP1L-ET1/ET2), is the protocol for fixed buffer communication the same as that of MICREX-F?
Yes, it is the same.
Show Detail
-
Is it possible to connect a recorder in parallel with signal input terminals of the thermocouple input module?
Yes, it is generally possible. However, be sure to use compensating leads also for wiring to the recorder.
Some recorders may not permit connection dependi...
Show Detail
- No:1420
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
Is it possible to use a function block (FB) inside FBs (nesting)? If it is possible, how deep is the nesting allowed to be?
Up to 127 levels of nesting is possible.
Show Detail
- No:1431
- Displayed Date:2023/04/25 19:00
- Category:
Application