No, you cannot. Use NW0H-CNV (RS-232C/RS-422 converter) or NP4H-CVU (USB/RS-422 converter) in combination with NW0H-CA3 Show Detail
Both Standard and Expert (D300win) are program loader software for the SX series. However, there is no compatibility between program data (called 'project')... Show Detail
Once a compilation error occurs during patch POU, the project must be compiled and downloaded again. Therefore, you need to stop the CPU. Please consider the... Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
Can I connect MICREX-F series and SX series P-link modules via P-link?
Yes, you can connect MICREX-F series and SX series P-link modules, and communicate between them. * For the connection and communication methods, see 'Sectio... Show Detail
You cannot upgrade 'MICREX-F PLC Programmer' free of change. 'MICREX-F PLC Programmer' that can be installed as NL4N-WNSB is currently included with the p... Show Detail
What is necessary for MODBUS_TCP communication between SPH and an external device?
The following are necessary. 1) Hardware Ethernet interface module (NP1L-ET1) or CPU module with built-in Ethernet (SPH2000/3000 series CPU types w... Show Detail
No, you cannot access the input (output) parameter (WV*, DV*) for which the data length is set in words/ double-words by using a bit address within the user ... Show Detail
There is a difference between 'Unpassive' and 'Fullpasisve' as follows. 1) Unpassive: Communicates with a device that has any IP or port No. 2) Fullpassi... Show Detail
I bought a USB 3.0 cable (A-B type) to connect to FLT-ASFKA. However, I cannot connect them.
FLT-ASFKA is equipped with a USB2.0 (B type) connector. The connecter shape is different between USB 3.0 (B type) and a USB 2.0 (B type). Purchase a USB 2.0 ... Show Detail