You cannot upgrade 'MICREX-F PLC Programmer' free of change. 'MICREX-F PLC Programmer' that can be installed as NL4N-WNSB is currently included with the p... Show Detail
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la... Show Detail
Can the D300win cable (Type_ NP4H-CB2) be extended?
It can be extended by connecting a commercially-available LAN straight cable by using the connection kit. Extending the cable makes it more susceptible to t... Show Detail
When you do not check 'RETAIN' on the variable worksheet (default), the variable is treated as a non-retain memory. When you check 'RETAIN,' the variable i... Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ... Show Detail
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later. [Related document] Refer to Section '11-7 Sampl... Show Detail
Is there a limit on the wiring length of P-link/PE-link cables?
Yes, both P-link and PE-link cables have limits on the wiring length. [P-link] ・Electrical transmission line Total length of electrical transmission ... Show Detail
Only when the MICREX-F CPU is F55/F70/F70S/F80H/F120H/F120S to F150S, you can connect a MICREX-SX series T-link interface module although the order of the bi... Show Detail
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor. Show Detail
171-180 of Total 398