No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
The SX control utility of the D300win V2 supports the P-link area monitoring function from V2.2.6.0 and later. Check the version. Note that all versions of... Show Detail
Does data monitoring of the I/O area require the module to be registered in the system definition?
Unless you register the module in the system definition and set the I/O group in the CPU parameters, data monitoring is disabled because no memory is reserve... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
Is it possible to use the M/L area in the user FB with the Standard Loader (Type_ NP4H-SWN)?
Yes_ however, it is not recommended in terms of program reuse. It is better to use internal memory such as M and L by connecting them to the I/O terminals ... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
Yes, you can. The SXPLC simulation function is supported by V3.0.14 or later version of Expert (D300win). Use the SXPLC simulator and SOFT MONITOUCH TE... Show Detail