When I downloaded a program to the CPU module, a fatal fault occurred. I checked fault diagnosis and found both the CPU and I/O modules were indica...
This is because the SX bus loop-back plug is not connected.
Connect a loop-back plug to the base board.
Show Detail
- No:1335
- Displayed Date:2023/04/25 19:00
- Category:
Error
-
With the Standard Loader (Type_ NP4H-SWN) version 2, colors can be specified for local timers and counters. How can I color them in print?
The Standard Loader does not support color printing.
Show Detail
-
With a positioning control module (Type_ NP1F-MP2/MA2), what are the statuses of the status information signals after power-up?
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1].
The interrupt input sig...
Show Detail
- No:1318
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:17
- Category:
Function
-
I understand that an analog input module (Type_ NP1AXH4-MR, etc.) has a signal line breakage detection function. How does it work?
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided.
An input voltage of 0.92 V or lower for the 1 to 5 V ran...
Show Detail
- No:1316
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
With the MICREX-SX SPH Series, when should I replace the battery after the battery error LED of the CPU module lights up?
It depends on your CPU model and how often you conduct regular inspection.
The backup time after a battery error is detected is as follows.
NP1PS-32/32R:...
Show Detail
- No:1312
- Displayed Date:2023/04/25 19:00
- Category:
Accessory
-
I'm developing software with D300win (V2.2.5.0). Is it possible to collect data for each scan of the PLC?
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later.
[Related document]
Refer to Section '11-7 Sampl...
Show Detail
-
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_
(1) Set the data within the user application
(2) Use 'PID FB parameter support ut...
Show Detail
- No:1296
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 14:18
- Category:
Function
-
Do Fuji Electric PLCs obtain JIS C 0508 (IEC 61508) 'Functional safety of electrical/electronic/programmable electronic safety-related systems'?
No, Fuji Electric general-purpose PLCs including the MICREX-SX series do not obtain it.
Show Detail
- No:1283
- Displayed Date:2023/04/25 19:00
- Category:
Others
-
When I write parameter to LonWorks module (NP1L-LW1) using support tool for a LonWorks (NP4N-LNDF), what is the required cable?
You don't need a dedicated cable.
Since the parameters will be set via the CPU module, you need a loader cable for the PLC and the program loader software.
Show Detail
-
When I set the high-speed counter module (NP1F-HC2) to the preset operation mode of the multi-functional counter FB, the preset is disabled in the ...
When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow.
Show Detail
- No:1675
- Displayed Date:2023/04/25 19:00
- Category:
Function