Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail
Can I increase the font size displayed on the Standard loader screen?
By changing the zoom rate of the main screen displaying a program or data monitoring, the on-screen font size is also increased or decreased. However, the S... Show Detail
The battery supplied with a CPU module is used to back up the following memories in the CPU module when a PLC system is turned off. Basically, connect the ba... Show Detail
How can I display the list of device use status on Standard loaderV3
1) Double-click the 'Device' icon in the project view to open the device window. 2) Click the [Device Type] selection button (▼) and select a device the u... Show Detail
I cannot download a project to the user ROM card inserted in the CPU. What is a possible cause?
This problem is probably caused by the following reasons: [For SPH300/2000/3000 series] 1) The CPU mode selection switch is not set at the 'UROM-TERM' pos... Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
The specified current value is constant regardless of the frequency because the input impedance for the pulse input I/F is fixed. Show Detail
In a redundant system, both CPUs are identified as CPU0 and you cannot read a battery error of the standby CPU. Determine the condition of the standby CPU fr... Show Detail