The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
This only stops the operating CPU and the operation is not switched to the standby CPU. Show Detail
The '.BSM' file is intended for manufacturers' maintenance purposes. You can check fault information by opening the '.RAS' file with Notepad or another tex... Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
_F_WRITE_CSV_DINT' may be influenced by the file search time depending on the number of files in the CF. The time it takes for 100 (200-word) DINT data to b... Show Detail
Instead of FNC120A-C10, can I use FNC130A-C10?
Yes, you can use FNC130A-C10 in combination with FNC120A-C10. Attach the same type of optical adapters at the both ends of the optical fiber. FNC130A has t... Show Detail
I want MICREX-SX SPH models adapted to tropical wetlands.
The standard MICREX-SX SPH models have been designed for use in tropical wetlands. Therefore, all you need to do is to order standard models. Show Detail
Which optical fiber cable for an SX bus should I choose for outdoor use?
Use an optical fiber cable (Type 2-C-LAP) provided by Sumitomo Electric Industries, Ltd. Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail