UI4 is not supported by the specification with the VB automation interface. Meanwhile, UI4 is supported by the custom interface specification. Show Detail
No, it cannot be used as it is. It requires resources to be added, the system configuration definitions to be changed, I/O groups to be reset and other ta... Show Detail
Is it possible to use the optical converter NP1L-OL1 between processors as with the P-link?
The optical converter NP1L-OL1 is an optical converter of the SX bus. It cannot be used because the SX bus is not a link between processors. Show Detail
Is there any way to back up the internal data of the CPU by using the loader?
Use the 'SX control utility' software. This software is included in both D300win and Standard software. The utility included in either of them has the ... Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail
I use structure variables with the D300win. How each elements in structure assigned in memory?
Unfortunately, the member assignment in the structure is not disclosed. Show Detail
One M_OPEN consumes one port of SPORT_NO, which is the local port. RPORT_NO is the port of the other end of the communication seen from the SX. Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
When the memory with a retain attribute is corrupted, the CPU clears the memory and operates in nonfatal fault condition. If the power is reset again in this... Show Detail
Yes, it is possible. Method 1): You can use the 'Backup' function of the SX control utility function in D300win V3.1 or later to save the internal data in ... Show Detail