In the redundant CPU system, the cycle of the default task takes 70 ms. It takes only several microseconds with a single-CPU system. Why is such a ...
Since the data equalization (data copying from the operating CPU to the standby CPU) is performed after the default task is processed, the larger the size of...
Show Detail
- No:1568
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
On the SX-Programmer StandardV3 (NP4H-SWN), I/O addresses (X, Y) I entered appear in red. Can I change the color?
The text color of I/O addresses (X, Y) is red. You cannot change it.
Show Detail
-
I mounted the power supply module (Type_ NP1S-22) on the base board (Type_ NP1BS-06). The connector at the far left of the base board is not used. ...
No, it doesn't.
A power supply module may occupy two slots (Type_ NP1S-22, NP1S-42) or one slot (Type_ NP1S-81, NP1S-91).
The connector at the far left...
Show Detail
- No:1340
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Main unit
-
If I order one SX bus loop-back plug (Type_ NP8B-BP), how many plugs will be delivered? Does it mean a set of two plugs?
An order for one NP8B-BP means one plug will be delivered.
If you need two plugs, order two pieces. The CPU module (Type_ NP1P***) and integrated type int...
Show Detail
- No:1338
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:34
- Category:
Accessory
-
Does the built-in ALM contact of the power supply module of SPH maintain its status (contact closed) even if the power supply recovers to normal af...
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open).
Show Detail
- No:1289
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
In Expert (D300win), I copied and pasted an existing timer (or counter) to add timer. However, a compilation error (Function block or structure cor...
Timers (or other FBs such as counters) each have an internal memory that is called an instance.
Therefore, after copying a timer, you need to define a vari...
Show Detail
-
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_
(1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist...
Show Detail
- No:1570
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
The physical environmental conditions of the MICREX-SX specify 'Free from corrosive gases.' Please specifically explain this environment.
The MICREX-SX is assumed to be installed inside a dustproof type switchboard in a general factory.
There is a wide variety of corrosive gas environments dep...
Show Detail
- No:1566
- Displayed Date:2023/04/25 19:00
- Category:
Others
-
Which is the signal that indicates pulse output completion on the positioning control module (Type_ NP1F-MP2)?
Pulse output completion is indicated by the 'Command pulse zero' signal.
Normally, it is '1' to indicate the status of completion. When the number of pulses...
Show Detail
- No:1548
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I have converted MICREX-F program to SX using StandardV3. After execute [Conversion All], many warning messages appear '*** (Function block (FB) na...
You can remove these warnings by deleting function blocks (FBs) that are not used in the program.
Do either of the following methods:
Method 1
1) After...
Show Detail