With D300win V2, I cannot monitor some of the variables in the global variable worksheet.
They cannot be monitored if the number of rows in the variable worksheet exceeds 2520. Divide the variable worksheet so that the number of rows is 2500 or... Show Detail
It is the same as the loader mode (mode switch 3) of the general-purpose communication module (Type_ NP1L-RS1/RS2/RS3/RS4/RS5). Show Detail
This is because frame data with the template file names (default names) are deleted at the time of uninstallation. (Files created with new names are not dele... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Can I change a PLC program without a programming tool?
With a CPU module of the SPH Series that supports user ROM cards (CF or SD), a user ROM card can be used to download a program to the CPU module. Show Detail
Can I store multiple programs in the user ROM card (CF or SD) ?
No, it is not possible. Only one program can be stored. Show Detail
Modules that use the processor bus, such as the P/PE link and FL-net modules, need be mounted on the slot equipped with the processor bus. Other communicati... Show Detail
You can display the mismatch circuit in the program and differences using the 'Verify' command of the Standard loader. After uploading the project from the... Show Detail
There are two ways to connect a USB port of a personal computer and a CPU: 1) Connect to the USB port of the CPU (directly connected to the USB cable). 2) ... Show Detail
This problem was probably caused by the following factors_ (1) Failed contact of the connector on the SPH, (2) Failed contact on the POD (UG), (3) Improp... Show Detail