There is a limit to the number of words for the I/O modules that can be mounted on a T-link expansion (Type_ NP1L-RT1) base_ 128. With the thermocouple inpu... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
The base board that plays the role of a hub of optical converter modules is not represented in the system definitions. When the power supply (PS) of the sam... Show Detail
There is a limit to the number of POUs that can be opened simultaneously_ 31 including 'Data 1,' 'Simulation' and 'AFB.' Show Detail
With D300win V2, I cannot monitor some of the variables in the global variable worksheet.
They cannot be monitored if the number of rows in the variable worksheet exceeds 2520. Divide the variable worksheet so that the number of rows is 2500 or... Show Detail
Can a master control instruction be used in the MICREX-SX Series?
(1) For Expert (D300win) No master control instruction is provided. This is because the MICREX-SX Series is dedicated to programmable logic controlle... Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail
Yes, there are. When you install an expansion FB, sample programs are installed as compressed projects (extension *.Zwt) in a folder named 'Zipped' under t... Show Detail
Is broadcast communication via Ethernet possible?
It is possible as long as the protocol is UDP/IP. In the M_OPEN FB, specify 255.255.255.255 as the IP address to be set for the 'communication destination s... Show Detail
When SX-Programmer Expert (D300win) was upgraded to V3.3.2.0, the 'IP address and gateway setting definition' was added to accommodate the function addition ... Show Detail