Set the number of timers according to the number actually used. By simply specifying 8192 or a larger value as the timer number, a global timer can be used. Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
The MICREX-SX is assumed to be installed inside a dustproof type switchboard in a general factory. There is a wide variety of corrosive gas environments dep... Show Detail
This problem was probably caused by the following factors_ (1) Failed contact of the connector on the SPH, (2) Failed contact on the POD (UG), (3) Improp... Show Detail
Usually, set the CPU No. to 0. The CPU No. 0 works as a master of an SX bus system. In a multi-CPU system or a CPU redundant system which uses multiple CPU ... Show Detail
What is the type of the configurator that is used with NP1L-PD1/PD2?
Use the following types of configurators: 'CONF-PDP' for NP1L-PD1 and 'NetTool for Profibus' for NP1L-PD2. Purchase a configurator from HMS Industrial Networ... Show Detail
You can use the following program as an alternative. When you turn on the differential command 'M0,' the differential output 'M2' turns ON for one scan. ... Show Detail
The version of the D300win is displayed as Version 4.0. Why?
This was probably caused by the following factors (1) The PC was not restarted after the D300win was installed. (2) A space is included in the name of the... Show Detail
Doesn't the connector type I/O module of the SPH Series include a connector as an accessory?
The SPH Series does not include an I/O connector. A soldering type connector is available as an option sold separately (NP8V-CN). Show Detail
Unfortunately, information in a device connected to the master module cannot be read even by building a user application. Please use the dedicated configura... Show Detail