After I replaced an Ethernet module (Type_NP1L-ET1/ET2), it cannot communicate with the target device. What is a possible cause?
The IP address and port standard No. of the self station of the Ethernet module are stored in the internal ROM of the Ethernet module. After replacing an Eth...
Show Detail
-
When I use the SX communication middleware (Type_ NP4N-MDLW) and specify (_) in the access path during the item registration for the client, Errno=...
Move to the item ID without using the access path on the client side (D_).
Show Detail
- No:1556
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
How long is the refresh cycle of the pulse count value data of the high-speed counter module (Type_ NP1F-HC2)?
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle...
Show Detail
- No:1547
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
I want to remotely monitor the status of the memory. Is it possible to use the SX control utility via an online adapter?
The Control Utility only supports the COM port and USB port and cannot be used.
Show Detail
- No:1397
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
How are data of the BOOL type defined for an array assigned in the actual memory? (How about when an array of 32 data of the BOOL type is specified...
Of the array element Nos., [0] is assigned to the 0th bit and [31] to the 31st bit.
Show Detail
- No:1345
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
Can I connect a MICREX-SX series T-link interface module (Type_NP1L-RT1) to a MICREX-F series T-link master module?
Only when the MICREX-F CPU is F55/F70/F70S/F80H/F120H/F120S to F150S, you can connect a MICREX-SX series T-link interface module although the order of the bi...
Show Detail
-
When I attempted to download a project to a CPU with user ROM card by using D300win, a message appeared saying 'Invalid loader command process!' an...
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform...
Show Detail
-
With the FL-net module (NP1L-FL1/FL2/FL3), is there any way to confirm that the data sent from the node-A have actually been received by the node-B?
When the common memory system is used, this can be achieved by handshaking with an application using part of the link memory.
Without handshaking, it is not...
Show Detail
-
Is it possible to use a PC application program to manipulate data that was written with the SX application (F_WRITE) onto the memory card inserted ...
The data written with the F_WRITE FB is in a binary format. Consequently, it can be manipulated with commercial binary editors.
Show Detail
- No:1623
- Displayed Date:2023/04/25 19:00
- Category:
Application
-
A nonfatal fault of the takt cycle monitoring error has occurred. What is a possible cause?
The takt cycle monitoring error is caused by the following factors_
(1) The preset takt cycle value specified in the system definition is shorter than the ac...
Show Detail
- No:1576
- Displayed Date:2023/04/25 19:00
- Category:
Error