No, you do not have to connect T-link devices in ascending order of address. In addition, you can assign addresses at some intervals for the future expans... Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
You can display the mismatch circuit in the program and differences using the 'Verify' command of the Standard loader. After uploading the project from the... Show Detail
It enables reception only when CD (Carrier Detection) is ON. (Other operations are the same as those in the DTE mode.) Show Detail
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't. Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica... Show Detail
The memory usage is displayed in 'GM (global memory)' by the 'Device' function that is used to edit tags or check the memory usage. However, the memory cap... Show Detail
The MICREX-SX series T-link also has the fail-soft operation function, but not the general fail-soft function. In MICREX-SX, fail-soft operation can be ind... Show Detail
What are <N-mode> and <SX mode> in the SPB series?
The SPB firmware has two operation modes: “N-mode” and “SX-mode.” Applicable personal computer loader varies depending on the firmware used. <N-mode&g... Show Detail
Is it possible to indirectly specify the timer set value with the Standard Loader (Type_ NP4H-SWN)?
Yes, it is possible. Input a memory address (DLxx) instead of an immediate value as the operand of the timer instruction. Show Detail
NP4H-CB2 cannot be combined with a BLACK BOX converter for use. Use NP4H-CB2 in combination with a converter NW0H-CNV (for RS-232C) or NP4H-CVU (for USB). Show Detail