(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks). (2) High-performance CPU_ Access takes place when a request is generated rega... Show Detail
Can I change a PLC program without a programming tool?
With a CPU module of the SPH Series that supports user ROM cards (CF or SD), a user ROM card can be used to download a program to the CPU module. Show Detail
The existing MICREX-F program does not need any modification. Show Detail
One possible cause is that common FB _C_COM is not registered with the library. For communication-related expansion FBs including _C_FREE, register common... Show Detail
This is because when a compilation process is carried out, automatically assigned variables (variables for which AT specification is not used) and FB instanc... Show Detail
The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail
Of the array element Nos., [0] is assigned to the 0th bit and [31] to the 31st bit. Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
In a CPU redundant system, how can I update a program while the system is running?
Refer to the following How-to Guide, which describes how to update a program while a redundant system is running. MICREX SX How-to Guide 'How to Change Prog... Show Detail
Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards. NP1L-FL1 : FL-netVer1 NP1L-FL2 : FL-netVer2 NP1L-FL3 : FL-netVer3(Class1) In FL-... Show Detail
121-130 of Total 398