I use the pulse train output positioning control module (Type_ NP1F-HP2). Please tell me the rated voltage/current of the pulse output and control ...
Both the pulse output and control output are open collector outputs. They should be used within the following ranges
(1) Pulse output_ 30 V DC, 40 mA or less...
Show Detail
- No:1602
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
In a redundant system (SPH300 or SPH2000 with StandardV3), when I change the program online (Load the changed program into PLC), is the changed pr...
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing
by, the changed program is loaded into both CPUs...
Show Detail
-
With a positioning control module (Type_ NP1F-MP2/MA2), what are the statuses of the status information signals after power-up?
The near zero signal/command pulse zero signal/positioning end signal/RDY signal of the status information signals are set to [1].
The interrupt input sig...
Show Detail
- No:1318
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/13 15:17
- Category:
Function
-
An existing P-link system is composed of MICREX-F. If part of it is replaced with P-link of MICREX-SX, does the existing MICREX-F program need to b...
The existing MICREX-F program does not need any modification.
Show Detail
-
With communication using RS-485 of a general-purpose communication module (Type_ NP1L-RS□), is there any means to detect a line disconnection?
While 'DTR_ terminal ready' can be used with RS-232C, this control line is not present for RS-485.
If no response is received while data are exchanged, re...
Show Detail
-
When I downloaded a program to the CPU module, a fatal fault occurred. I checked fault diagnosis and found both the CPU and I/O modules were indica...
This is because the SX bus loop-back plug is not connected.
Connect a loop-back plug to the base board.
Show Detail
- No:1335
- Displayed Date:2023/04/25 19:00
- Category:
Error
-
I find the TER_LED of the T-link master module (Type_ NP1L-TL1) sometimes illuminated. The communication speed is lowered when it occurs.
It may be caused by noise. Check the surrounding environment and wiring routes for any problem.
The lowered communication speed is assumed to be because t...
Show Detail
-
The variables I specified as retained by using D300win are not retained through a power failure. What can I do to solve the problem?
If battery-less operation is enabled under the 'CPU running definition' setting, the content of the retain memory is not retained. Disable battery-less opera...
Show Detail
-
Does the PROFIBUS-DP master/slave module (Type_ NP1L-PD1/PS1) support the DPV1 (message communication) function?
No, it does not support the DPV1 function.
It supports the DPV0 (I/O communication) function.
Show Detail
-
I want to expand the T-link expansion (T-link interface module Type_ NP1L-RT1) by further adding a base. Can I do this expansion by using the SX bus?
T-link or other expansion bases cannot be added by the SX bus.
Show Detail