Can I use a commercially available hub for FL-net modules?
We recommend you use an unmanaged switch, without B.S protection that is an industrial hub fulfilling the conditions of use for FL-net. * What is 'B.S'?... Show Detail
What is necessary for MODBUS_RTU communication between SPH and an external device?
The following are necessary. 1) Hardware: General-purpose communication module (NP1L-RS1/RS2/RS3/RS4/RS5) whose firmware version is V42 or later ... Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
No, you cannot use NW0H-CNV. The RS-232C/422 converter for personal computer loaders (Type_NW0H-CNV) needs to be supplied power from the PLC side, however, t... Show Detail
The influence of external resistance on the thermocouple input is approximately 0.3 ?V/?. The measurement accuracy of the thermocouple input is affected by... Show Detail
It is not provided as internal memory. You need to create the circuit shown in the attached diagram. The example shows a circuit in which M0 repeats ON and O... Show Detail
To input the initial value, input '[value, value, ..., value].' In brackets, input values and use commas to separate values. Show Detail
It is not possible with D300win V2. The sampling trace function is supported by D300win V3.1.1.0. or later. [Related document] Refer to Section '11-7 Sampl... Show Detail
The minimum required products are (1) High-performance CPU exclusively for the electronic cam, (2) pulse train combined module (Type_ NP1F-MP2) or anal... Show Detail
It is possible by preparing two types of power supply for driving the transistor device and the load. Refer to the User's Guide, which provides explanatio... Show Detail