Can I replace NP1L-FL2 with NP1L-FL3 for FL-net communication?
When connected via 10BASE-T, you can replace it. There is no need to change the system definition. Before replacement, set the switches on the front of the N... Show Detail
The influence of external resistance on the thermocouple input is approximately 0.3 ?V/?. The measurement accuracy of the thermocouple input is affected by... Show Detail
The '*' symbol on the ladder bus indicates a circuit being changed online. It will disappear when you transfer the changed circuit to the PLC. Show Detail
Compatibility between versions of D300win is upward compatibility. Using a lower version to extract a file causes no problem as long as no unsupported functi... Show Detail
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
Data with an address with the smaller number is arranged on the lower-order side. For example, DM0 consists of two words_ WM0 and WM1. WM0 is arranged on th... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
I am using D300win to write a program. Is there any fixed data type for direct address variables?
Bit data are of the BOOL type, 16-bit data the WORD type and 32-bit data the DWORD type. Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail
Is it possible to indirectly specify the timer set value with the Standard Loader (Type_ NP4H-SWN)?
Yes, it is possible. Input a memory address (DLxx) instead of an immediate value as the operand of the timer instruction. Show Detail