Create one project file. There are separate tasks for the respective CPUs and the assignment of POUs to tasks determines the CPU to which the program is a... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing by, the changed program is loaded into both CPUs... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
Is there any simple way of delivering PLC operation data set with Excel to the PLC?
The SPH2000/3000 Series have a function of reading data in CSV file format to the memory in the CPU (CSV interface FB provided by Fuji Electric). The data t... Show Detail
The MICREX-SX is assumed to be installed inside a dustproof type switchboard in a general factory. The amount of dust mentioned above is assumed to cause no... Show Detail
The Control Utility only supports the COM port and USB port and cannot be used. Show Detail
NP4H-CB2 cannot be combined with a BLACK BOX converter for use. Use NP4H-CB2 in combination with a converter NW0H-CNV (for RS-232C) or NP4H-CVU (for USB). Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail