Can we use an FL-net module (Type_ NP1L-FL1/FL2/FL3) and standard LAN device with same network?
It is not possible. Each module comply to following FL-net standards. NP1L-FL1 : FL-netVer1 NP1L-FL2 : FL-netVer2 NP1L-FL3 : FL-netVer3(Class1) In FL-... Show Detail
When SX-Programmer Expert (D300win) was upgraded to V3.3.2.0, the 'IP address and gateway setting definition' was added to accommodate the function addition ... Show Detail
How can I create a double-word counter with the Standard Loader (Type_ NP4H-SWN)?
Use an add instruction with the double-word operand to increment by 1 (+1). Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
The Loader command mode is fixed to the TCP/IP communication. UDP/IP communication is not supported. Show Detail
The simulation function of the StandardV3 does not support the index register. Check the program operation using a hardware PLC. Show Detail
The communication specification of the remote master does not control remote devices by the station No. Therefore, you cannot register remote devices as 'No ... Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
If you start multiple Expert loaders (max. 2) earlier than V3.6.7, the one started later always goes into reference mode, which you cannot exit. To edit mu... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail