The error occurs because the address display mode is set to 'FLEX-PC,' but the address representation of the word device is not hexadecimal. For the addres... Show Detail
This is because the SX bus loop-back plug is not connected. Connect a loop-back plug to the base board. Show Detail
What standards does the MICREX-SX series comply with?
Fuji Electric website provides information on the standards that the MICREX-SX series complies with. Visit the following URL. Show Detail
They are retained. Note, however, that they are cleared if the power of the FL-net module is turned off. Show Detail
When SX-Programmer Expert (D300win) was upgraded to V3.3.2.0, the 'IP address and gateway setting definition' was added to accommodate the function addition ... Show Detail
When using Cfr32, are the start code, end code, and BCC included in the maximum data size?
Yes, they are. The maximum size is 32 words including the actual data, start code, end code, and BCC. (The same applies to _Cfr64, _Cfr128, _Cfr252, and _Cfr... Show Detail
When replacing SPB (N mode) with SPF, can I use the program without change?
SPF does not support N mode. Therefore, to use the program of SPB (N mode) in SPF, you need to convert it. Refer to the following manual for how to conve... Show Detail
Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module. Show Detail
This problem was probably caused by the following factors_ (1) Failed contact of the connector on the SPH, (2) Failed contact on the POD (UG), (3) Improp... Show Detail
The '*' symbol on the ladder bus indicates a circuit being changed online. It will disappear when you transfer the changed circuit to the PLC. Show Detail