I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?

Fuji Electric Global

Global
  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Communication (Others) > I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?
  • No : 1644
  • Displayed Date : 2023/04/25 19:00
  • Print

I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?

I use DeviceNet interface module (NP1L-RD1) under DeviceNet master (NP1L-DN1). How can I specify NP1L-RD1 in the system definition?
Category : 

Answer

In the system definition, group-type slave stations in any I/O configuration are registered as 'DeviceNet capsule.' In addition, the numbers of input and output words to be registered in the capsule parameter are the numbers of total words of the input and output modules to be mounted respectively.