When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decreasing...' What does this message mean?

  • Font Size
  • S
  • M
  • L
  • GLOBAL > PLC > SPH > Error > When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decrea...
  • No : 1502
  • Displayed Date : 2023/04/25 19:00
  • Print

When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decreasing...' What does this message mean?

When I compiled a project created in D300win, a warning message appeared saying 'The remainder capacity of the High speed PG memory has been decreasing...' What does this message mean?
Category : 

Answer

The SPH3000 series has 'high-speed program (high-speed PG) memory' area in the program memory.
When you store a POU in this area, the POU execution speed becomes approximately three times faster.
The warning message means that the high-speed program memory space is low.
F.Y.I
If there is not enough high-speed PG memory to assign a POU, for example, by adding a circuit to the POU, the POU is assigned to the normal area.
Preferentially assign POUs that need to be processed at a high-speed to the high-speed PG memory, which is fixed to 224K bytes. Execute also the optimized compilation (compression of the execution codes) of the POUs assigned to the high-speed PG area, and re-assign the POUs of a low-priority task to the normal area.