- No : 1316
- Displayed Date : 2023/04/25 19:00
-
Print
I understand that an analog input module (Type_ NP1AXH4-MR, etc.) has a signal line breakage detection function. How does it work?
I understand that an analog input module (Type_ NP1AXH4-MR, etc.) has a signal line breakage detection function. How does it work?
- Category :
-
Answer
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided.
An input voltage of 0.92 V or lower for the 1 to 5 V range and an input current of 3.68 mA or smaller for the 4 to 20 mA range are regarded as line breakage.