For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
It is possible by preparing two types of power supply for driving the transistor device and the load. Refer to the User's Guide, which provides explanatio... Show Detail
Doesn't the connector type I/O module of the SPH Series include a connector as an accessory?
The SPH Series does not include an I/O connector. A soldering type connector is available as an option sold separately (NP8V-CN). Show Detail
The influence of external resistance on the thermocouple input is approximately 0.3 ?V/?. The measurement accuracy of the thermocouple input is affected by... Show Detail
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor. Show Detail
Yes, it is generally possible. However, be sure to use compensating leads also for wiring to the recorder. Some recorders may not permit connection dependi... Show Detail
Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca... Show Detail
The product type without 'RI' judges ON/OFF of the inputs by current. On the other hand, the product type with 'RI' judges ON/OFF of the inputs by voltage. ... Show Detail
The temperature measurement value of the resistance temperature sensor (PT input) is unstable.
If this is caused by a fluctuation in the input temperature, moving average processing shown below may improve the condition. 1) Change the digital filter v... Show Detail
No, you can't. The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ... Show Detail
1-10 of Total 14