The influence of external resistance on the thermocouple input is approximately 0.3 ?V/?. The measurement accuracy of the thermocouple input is affected by... Show Detail
The temperature measurement value of the resistance temperature sensor (PT input) is unstable.
If this is caused by a fluctuation in the input temperature, moving average processing shown below may improve the condition. 1) Change the digital filter v... Show Detail
Doesn't the connector type I/O module of the SPH Series include a connector as an accessory?
The SPH Series does not include an I/O connector. A soldering type connector is available as an option sold separately (NP8V-CN). Show Detail
Is there an analog module that supports the moving average function?
The following analog input modules have the moving average function. 1) For the following models, the moving average function can be set by switch setting ... Show Detail
The measurement accuracy does not include zero junction compensation accuracy. The zero junction compensation accuracy is ±1°C (at ambient temperature 0°C ... Show Detail
Since the conversion accuracy after a scaling change remains within the specifications, rescaling is unnecessary. Show Detail
No, you can't. The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
It is possible by preparing two types of power supply for driving the transistor device and the load. Refer to the User's Guide, which provides explanatio... Show Detail
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor. Show Detail