When uploading a project from CPU, the error message 'Ex.FB that import is done was not found. Import the Ex.FB using the program import function' ...
If the project that you want to upload includes expansion FBs provided by Fuji Electric, the expansion FBs must be installed on your computer. Install the ex...
Show Detail
- No:1662
- Displayed Date:2023/04/25 19:00
-
To debug a PLC program without I/O module, I set I/Os as 'no equipment'. Then, I tried to set input contact (X) using switch of MONITOUCH. However,...
In Standard loader, to access the input memory from MONITOUCH, cancel the I/O group setting of the input specified as 'no equipment.'
If the input specified...
Show Detail
- No:1658
- Displayed Date:2023/04/25 19:00
- Updated DTM:2023/06/09 14:04
-
I use MICREX-SX Programmer Standard (Type_NP4H-SWN). Is it compatible with CPU modules of old versions?
To use conversion instructions from MICREX-F (instructions with the suffix '_MF') with SH2000 or SPH3000 series, the following software version of the CPU is...
Show Detail
- No:1314
- Displayed Date:2023/04/25 19:00
-
I converted SEL/DSEL instructions of MICREX-F to SX referring to manual FEH588-2. However, warning appeard 'DL** is overlapped with address range f...
This warning appears when the memory (DL) that is assigned to file declaration created for the timer/counter current values overlaps
with the DL memory that...
Show Detail
- No:1653
- Displayed Date:2023/04/25 19:00
-
On the StandardV3 loader, the memory usage of a processor link module such as a P/PE-link or FL-net module cannot be displayed. Can I check the mem...
The memory usage is displayed in 'GM (global memory)' by the 'Device' function that is used to edit tags or check
the memory usage.
However, the memory cap...
Show Detail
- No:1484
- Displayed Date:2023/04/25 19:00
-
In a redundant system (SPH300 or SPH2000 with StandardV3), when I change the program online (Load the changed program into PLC), is the changed pr...
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing
by, the changed program is loaded into both CPUs...
Show Detail
- No:1647
- Displayed Date:2023/04/25 19:00
-
I converted an M/F program into an SX program with the Standard loader. I performed simulation of the converted program in the Standard loader, but...
The simulation function of the StandardV3 does not support the index register.
Check the program operation using a hardware PLC.
Show Detail
- No:1471
- Displayed Date:2023/04/25 19:00