No, the Ethernet module does not support the AUTO-MDI/MDIX function (Auto-switching of straight/cross cable.) The applicable cable type depends on whether ... Show Detail
The amounts of data transmitted or received are not limited as R_WRITE instruction/R_READ instruction but by the capacity of the memory from/to which data ar... Show Detail
The IP address and port standard No. of the self station of the Ethernet module are stored in the internal ROM of the Ethernet module. After replacing an Eth... Show Detail
One M_OPEN consumes one port of SPORT_NO, which is the local port. RPORT_NO is the port of the other end of the communication seen from the SX. Show Detail
How many units of Ethernet module (Type_ NP1L-ET□) can be used in a system?
Up to 4 units can be connected in 1 configuration (on 1 SX bus). Note, however, that they must be configured so that the total number of units of other comm... Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail
I use the Ethernet module (Type_NP1L-ET1). Is the IP address assigned automatically?
The IP address is not assigned automatically. (DHCP function is not supported.) The default IP address is '192.168.0.1'. You can check the IP address b... Show Detail
It is possible with the Ethernet module software version V36 or later by using the F_READ (read)/F_WRITE (write) FB. After writing, the power (or reset) o... Show Detail
It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
11-20 of Total 25