It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
The D300win cannot connect to the SX via the Ethernet module.
The IP address of the Ethernet module will become effective when the power supply is turned off once and then turned on again after the module driver is dow... Show Detail
One M_OPEN consumes one port of SPORT_NO, which is the local port. RPORT_NO is the port of the other end of the communication seen from the SX. Show Detail
Yes, it is the same. Show Detail
The SPH system automatically inherits information such as the communication ports and reopening processing is not required. Show Detail
(1) Standard CPU_ Access takes place when tasks end (synchronized with tasks). (2) High-performance CPU_ Access takes place when a request is generated rega... Show Detail
No, you can't. You can check the IP address by connecting the PC loader to the CPU module and monitoring the RAS information of the fault diagnosis function. Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
In the parameter setting of the Ethernet module in the system definition, set the 'Server FTP command watch timer value' to 0. The port is not closed even if... Show Detail
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU. For the CPU to recognize the Ethe... Show Detail