The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
Only open-collector (single-ended) signals are accepted. (NP1F-HC2 accepts differential signals.) The rated current is 40 mA and an encoder that permits t... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
What measures can I take against external noise of the high-speed counter (Type_ NP1F-HC2)?
Use the recommended shielded twisted pair cable mentioned in the User's Manual. Also provide shielding. Show Detail
The module is equipped with 2 channels of high-speed counter and signals of a different voltage can be counted for each channel. To set the signal level, s... Show Detail
For PID control by using a PID FB package, how should I set the various parameters?
For setting parameter values (such as P, I and D), it is possible to_ (1) Set the data within the user application (2) Use 'PID FB parameter support ut... Show Detail
When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow. Show Detail
41-50 of Total 50