The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail
When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow. Show Detail
The minimum required products are (1) High-performance CPU exclusively for the electronic cam, (2) pulse train combined module (Type_ NP1F-MP2) or anal... Show Detail
The counter is initially set to gate mode. Counting is disabled unless you provide a 'gate signal' externally by hardware or set 'gate disabled' by software.... Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
21-30 of Total 50