How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
Pulse input type_ A-phase for the pulse and B-phase for the sign. Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail