When the CPU module is stopped, the positioning operation stops. Show Detail
Pulse output completion is indicated by the 'Command pulse zero' signal. Normally, it is '1' to indicate the status of completion. When the number of pulses... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
On the positioning module (Type_NP1F-MP2/MA2), the 'ERR' LED turns ON. What are the possible causes?
A possible cause is that a “Deviation amount over error” occurred. For details, refer to the user's manual FEH213 (NP1F-MA2) or FEH214 (NP1F-MP2) 'Section 8 ... Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
The module counts feedback pulses even without Z-phase pulse signals. Note that when Z-phase pulse signals are not provided, origin return operation is dis... Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail