You can refer to sample project Mptpf4.zwt stored in the ZIPPED folder in the D300win folder. Show Detail
Pulse output completion is indicated by the 'Command pulse zero' signal. Normally, it is '1' to indicate the status of completion. When the number of pulses... Show Detail
When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft... Show Detail
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req... Show Detail
On the positioning module (Type_NP1F-MP2/MA2), the 'ERR' LED turns ON. What are the possible causes?
A possible cause is that a “Deviation amount over error” occurred. For details, refer to the user's manual FEH213 (NP1F-MA2) or FEH214 (NP1F-MP2) 'Section 8 ... Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
11-20 of Total 50