You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
Check the following two points (1) To use the EMG/±OT signal, input the 'External power supply 24 V DC.' (2) Check the wiring of the external equipment. (T... Show Detail
What is the dummy module (Type_ NP1F-DMY) used for? Is it required for an unused slot?
In an SX system, removing any I/O module that has failed causes the CPU to stop running due to a 'system definition mismatch.' In a case like this, a dummy ... Show Detail
No, it is not possible. Use an encoder of the line-driver or open-collector output type. When using a line-driver type, pay attention to the output capacity ... Show Detail
One possibility is that the compare value is not stored in the compare register of the high-speed counter. The compare value is written by turning the data w... Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
The NP1F-HC2 constantly continues updating the pulse count value data for the SX bus I/F in a cycle of 200 ?s (fixed). The count data, however, will be refle... Show Detail
On the positioning module (Type_NP1F-MP2/MA2), the 'ERR' LED turns ON. What are the possible causes?
A possible cause is that a “Deviation amount over error” occurred. For details, refer to the user's manual FEH213 (NP1F-MA2) or FEH214 (NP1F-MP2) 'Section 8 ... Show Detail
You can refer to sample project Mptpf4.zwt stored in the ZIPPED folder in the D300win folder. Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail