In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
While NP1F-HC2 requires an external power supply of 5 V DC, NP1F-HC8 produces 5 V DC within the module from an external 24 V DC power supply and does not req... Show Detail
Since the parameter data area of the positioning control module (Type_ NP1F-MP2/MA2) operates on the RAM, it is always cleared when you turn off the module. ... Show Detail
How do I perform pulse output with the high-speed output module (Type_NP1Y32T09P1-A)?
All the channels in the high-speed output module are set to the general purpose output mode (normal digital output) by default. To use the module in the pul... Show Detail
How do I use a manual pulse generator with the positioning module (Type_NP1F-MP2/MA2)?
Set the I/O area of the positioning module following the steps below. 1) Set 'h1C00' in the offset word address +16 (Ch1 Set value area: Low word). (Set ... Show Detail
On the positioning module (Type_NP1F-MP2/MA2), the 'ERR' LED turns ON. What are the possible causes?
A possible cause is that a “Deviation amount over error” occurred. For details, refer to the user's manual FEH213 (NP1F-MA2) or FEH214 (NP1F-MP2) 'Section 8 ... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
When the CPU module is stopped, the positioning operation stops. Show Detail
When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
11-20 of Total 50