When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail
The four-axis pulse string output terminal module (Type_ NR1SF-HP4DT) does not have a physical ±OT terminal. You can solve this problem by using software a... Show Detail
The MICREX-SX series positioning module 'Type_NP1F-HD2A' replaces NC1F-VP1/FGU130B. Be aware of the following points: 1) NP1F-HD2A is differential output t... Show Detail
Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
Both the pulse output and control output are open collector outputs. They should be used within the following ranges (1) Pulse output_ 30 V DC, 40 mA or less... Show Detail
Is electronic cam operation possible without using the dedicated module?
No, it is not possible. Combine the electronic cam FB package (Type_ NP4N-CAMFV3) with a positioning control module (Type_ NP1F-MP2/MA2). Show Detail
Pulse input type_ A-phase for the pulse and B-phase for the sign. Show Detail
In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail