Pulse counting is disabled on the high-speed input module (Type_ NP1X3206-A). What should I check?
Check the following points_ (1) Check the input form specified on the application program. (2) Set Enable counting to '1.' If the pulse count data regist... Show Detail
Possible causes include a fuse blowout in the high-speed output module (Type_ NP1Y32T09P1-A). Show Detail
One loop of control requires FB instances of about 300 words. Accordingly a CPU with FB instances for at least 18 K words is required. This leads to the conc... Show Detail
It might be counting noise as a pulse. Take the following measures_ (1) Isolate the pulse generator and PLC from the noise source and shorten the wiring dist... Show Detail
What measures can I take against external noise of the high-speed counter (Type_ NP1F-HC2)?
Use the recommended shielded twisted pair cable mentioned in the User's Manual. Also provide shielding. Show Detail
In PPID, a POU for the PID FB package, which range does the % of proportional band P account for?
Proportional band P is the % of the variation range of input PV required for the change of output MV in the effective variation range from 0 to 100%. It is... Show Detail
Yes, all points can be used. Regarding the pulse width, pulse signals with a width down to 20 us can be captured with ports 1 to 8. With ports 9 to 32, pu... Show Detail
Pulse input type_ A-phase for the pulse and B-phase for the sign. Show Detail
This was probably caused by one of the following two factors_ (1) ±OT is set to 'Disabled' in the parameter setting of the positioning control module (Type_... Show Detail
Check the feedback pulse wiring (to make sure that a shielded twisted pair is used, wiring conditions are appropriate, etc.). One possible reason for the c... Show Detail
11-20 of Total 50