When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow. Show Detail
In the MV selection part in the PID FB, (1) the backward operation uses the internally calculated MV value (%) without processing it (as-is)_ and (2) the for... Show Detail
Check to make sure that_ (1) The channel specification (CH_SEL) is correct. (2) The FB instance names are not duplicated. (3) The preset command is given aft... Show Detail
Note the following points (1) The rated output voltage is 12 to 24 V. Check the voltage of the device to be connected. (2) The Z-phase/timing input signal f... Show Detail
If the start bit remains on, the positioning end signal is not generated. Show Detail
In the standard expansion counter FB _MHCNTH, CH0 operates but CH1 does not.
It seems that this problem was caused by an improper address setting for INDAT/OUTDAT assigned to the counter FB terminal. On a single module, assign the sa... Show Detail
You can check it with the status indication LED on the front of the module. When a low battery voltage is detected, the CER LED on the front of the module ... Show Detail
What measures can I take against external noise of the high-speed counter (Type_ NP1F-HC2)?
Use the recommended shielded twisted pair cable mentioned in the User's Manual. Also provide shielding. Show Detail
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used. Show Detail
When the EMG signal and ±OT signal are not used, connect them to 24 V DC. Alternatively, you can set the ±OT signal to 'Disabled' in the parameter settings ... Show Detail