No, it doesn't. A power supply module may occupy two slots (Type_ NP1S-22, NP1S-42) or one slot (Type_ NP1S-81, NP1S-91). The connector at the far left... Show Detail
The SX bus station number for the slot on which the CPU module is mounted is recognized as unused. Show Detail
Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail
If the CPU modules are mounted on a hot plug base board with station No. setup function, you can replace them without turning off the power. Show Detail
For what application is the base board with station number setting switch used?
It is used as a base specified for 'system fail-soft start-up' operation, which is set when there is any base with some modules on which power is not turned ... Show Detail
You should be careful because if the write protection is OFF, the ROM is rewritten simultaneously with the internal RAM of the CPU during program download. Show Detail
The rated current is 3 A. Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
You cannot access general memory other than the memory for the multi-CPU from the other CPU. Access using the direct read/write FB is used for the access to ... Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail