The P-link memory is prepared in the P-link module. It is separate from the memory in the CPU and no change takes place at the time of switchover to a standb... Show Detail
Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Clock adjustment is initiated from CPU0 (operating) to other CPUs (standby). It takes place on a constant (1-minute) cycle at the time of and after system st... Show Detail
You can use it as a standard base board by setting its station No. to '00.' In this case, you also need to set the system definition of the loader designed f... Show Detail
The battery supplied with a CPU module is used to back up the following memories in the CPU module when a PLC system is turned off. Basically, connect the ba... Show Detail
Check the following system memory. (1) Configuration information %MW10.52 to %MW10.67 (WSM52 to 67) (2) Configuration fault information %MW10.68 to %MW1... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
Can I remove user ROM card in the CPU module (CF or SD) while the CPU is running?
A user ROM card can be inserted and removed when the UROM LED is not illuminated (the key switch is set to a position other than UROM). When removing it whi... Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
You cannot access general memory other than the memory for the multi-CPU from the other CPU. Access using the direct read/write FB is used for the access to ... Show Detail
21-30 of Total 34