Is there an alarm output contact to use when an error occurs in the PLC system?
For an alarm contact output of an error of the PLC system, select an arbitrary output module in the system definitions and define its 0th bit as a 'system DO... Show Detail
Is it permitted to have an unused slot in an SPH system configuration?
An unused slot is permitted in a system configuration. If you plan to mount a module in the unused slot in the future, it can be registered as 'unimplemen... Show Detail
You should be careful because if the write protection is OFF, the ROM is rewritten simultaneously with the internal RAM of the CPU during program download. Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
The equivalent data is retained for one default task during switching and the standby CPU starts execution from the beginning of the task. Show Detail
If the CPU modules are mounted on a hot plug base board with station No. setup function, you can replace them without turning off the power. Show Detail
There is no loader at the site. Is there any way to change the program?
If the CPU supports user ROM (CF or SD card), you can do it by sending the program data for operation to the site by e-mail or another method and then transf... Show Detail
No, they do not have polarity because they use relay contacts. Show Detail
When you use battery-less operation on the SPH, is the history of RAS information recorded?
During battery-less operation, previous fault information and other 'history of RAS' are not saved. Only the present RAS information is displayed. Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
11-20 of Total 34