When the CPU module is stopped, the positioning operation stops. Show Detail
The SPH system automatically inherits information such as the communication ports and reopening processing is not required. Show Detail
Can I remove user ROM card in the CPU module (CF or SD) while the CPU is running?
A user ROM card can be inserted and removed when the UROM LED is not illuminated (the key switch is set to a position other than UROM). When removing it whi... Show Detail
To use conversion instructions from MICREX-F (instructions with the suffix '_MF') with SH2000 or SPH3000 series, the following software version of the CPU is... Show Detail
Yes, it is the same. Show Detail
T-link or other expansion bases cannot be added by the SX bus. Show Detail
I want to relay the SX bus optical cable. Is it possible?
Yes, it is possible. Note that one relay causes attenuation of about 1 dB. The allowable attenuation is 7 dB in total. Careful consideration is required be... Show Detail
Do not install an I/O terminal (Type_NR1S*-*, NR1T*-*, NR1J*-*, and NR1D*-*) on the floor of the panel because it has no ventilation slit for cooling. You ca... Show Detail
You can use it as a standard base board by setting its station No. to '00.' In this case, you also need to set the system definition of the loader designed f... Show Detail
Yes, a CPU is necessary. In the case of a system with no CPU, the input status LED does not work even if signals are externally input into the input module. Show Detail