No, you cannot. Use the dedicated loader cable (Type_NW0H-CA3). Show Detail
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing by, the changed program is loaded into both CPUs... Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
For an analog input range (1 to 5 V or 4 to 20 mA), a line breakage detection function is provided. An input voltage of 0.92 V or lower for the 1 to 5 V ran... Show Detail
In the PID FB, why is the integration time set by the number of periods and not by ms?
The PID FB is assumed to be processed in a periodic task. The integration time is calculated by multiplying the periodic task period in ms by the number of p... Show Detail
I cannot download a project to the user ROM card inserted in the CPU. What is a possible cause?
This problem is probably caused by the following reasons: [For SPH300/2000/3000 series] 1) The CPU mode selection switch is not set at the 'UROM-TERM' pos... Show Detail
The SX bus connector of the SPH300EX (Type_ NP1PS-74D) is an OUT (output) connector. When you connect SX bus equipment, connect the cable to the IN (input)... Show Detail
The SPH does not have a RUN contact. Is there any alternative?
As an alternative, you can combine hardware and software functions. (1) Hardware_ Prepare a relay output card and use one point as a RUN contact. (2) Sof... Show Detail
The IP address and port standard No. of the self station of the Ethernet module are stored in the internal ROM of the Ethernet module. After replacing an Eth... Show Detail
There is a possibility of mismatch between the project in the user ROM card and the CPU memory. On the 'Failure diagnosis' dialog, check the 'Resource inform... Show Detail