When I try to register a remote I/O master module using the I/O extension function in a multi-CPU configuration in the system definition, an error ...
No, you cannot use the I/O extension function in a multi-CPU configuration.
Register a remote I/O master module in the normal mode or extension mode in a...
Show Detail
- No:1651
- Displayed Date:2023/04/25 19:00
- Category:
Support tool
-
I use the Ethernet module (NP1L-ET1/ET2) and using communication FB (M_OPEN). M_OPEN sets two ports of RPORT_NO and SPORT_NO. Does this mean that o...
One M_OPEN consumes one port of SPORT_NO, which is the local port.
RPORT_NO is the port of the other end of the communication seen from the SX.
Show Detail
-
What is the rated current value of the fuse in the power supply module (NP1S-22)? I want to know to select the circuit breaker on the primary side ...
The rated current is 3 A.
Show Detail
- No:1641
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
I will use the analog voltage input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
Yes, you can. Note, however, that the input impedance reduces to half. Pay attention to the drive ability of the sensor.
Show Detail
- No:1622
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
I want to access the data memory in the MICREX-SX CPU from a PC via the RS-232C port of the general-purpose communication module. (Data read/write)
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode.
Various loader commands have been...
Show Detail
-
I will use the analog current input module. Can I input a single input signal to two CHs of the module simultaneously (in parallel) to use them?
No, you can't.
The relationship between i, which is the sensor output current, and i1 and i2, which are the CH input currents of the PLC, is expressed as i ...
Show Detail
- No:1603
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
I have connected the SPH Series with the POD (UG Series) via the T-link. A code F8 is displayed on the screen of the POD. What is a possible cause?
This problem was probably caused by the following factors_
(1) Failed contact of the connector on the SPH,
(2) Failed contact on the POD (UG),
(3) Improp...
Show Detail
-
Can I use a commercial LAN cable for the SX bus instead of the dedicated cable?
No, you can't.
Although the connection of the sending/receiving wires of the SX bus cable is the same as that for a commercial LAN cable (cross), the dedica...
Show Detail
- No:1557
- Displayed Date:2023/04/25 19:00
- Category:
Accessory
-
Which is the signal that indicates pulse output completion on the positioning control module (Type_ NP1F-MP2)?
Pulse output completion is indicated by the 'Command pulse zero' signal.
Normally, it is '1' to indicate the status of completion. When the number of pulses...
Show Detail
- No:1548
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Does the Ethernet module of the MICREX-SX (Type_ NP1L-ET1/ET2) support TCP/IP multicast transmission (sending/receiving)?
No, it does not support multicast transmission (sending/receiving).
It does support broadcast transmission (sending/receiving).
Show Detail