When I set offset on the analog module (NP1AXH8I-MR) by using software (parameters) and disable the software offset setting by operating hardware (...
After changing the range with the rotary switch, turn off the power once and then turn it on again, and the software offset setting will be disabled.
Show Detail
- No:1667
- Displayed Date:2023/04/25 19:00
- Category:
I/O
-
In a redundant system (SPH300 or SPH2000 with StandardV3), when I change the program online (Load the changed program into PLC), is the changed pr...
When the working CPU is running (in a normal or a nonfatal fault condition) and the standby CPU is standing
by, the changed program is loaded into both CPUs...
Show Detail
-
I want to access the data memory in the MICREX-SX CPU from a PC via the RS-232C port of the general-purpose communication module. (Data read/write)
You can access the memory from a PC by setting the general-purpose communication module (Type_ NP1L-RS2) to 'Loader' mode.
Various loader commands have been...
Show Detail
-
How can I provide Z-phase pulses when the equipment connected with the positioning control module (Type_ NP1F-MP2/MA2) uses a stepping motor?
Use the 'Excitation timing output' signal for the Z-phase pulse when a stepping motor is used.
Show Detail
- No:1574
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
Which FL-net unit is responsible for refreshing data of the common memory with FL-net modules (Type_ NP1L-FL1/FL2/FL3)? Where is the master station?
Refreshing data in the link data area in FL-net takes place when data is received from another station. The local station data is refreshed by sending the la...
Show Detail
-
When I use an Ethernet module (Type_ NP1L-ET□) to download the system definitions and module driver, a file transfer error is generated. Why?
The file transfer error occurs because the module driver is downloaded with the Ethernet module not recognized by the CPU.
For the CPU to recognize the Ethe...
Show Detail
-
In a CPU redundant system, how can I update a program while the system is running?
Refer to the following How-to Guide, which describes how to update a program while a redundant system is running.
MICREX SX How-to Guide 'How to Change Prog...
Show Detail
-
When I set the high-speed counter module (NP1F-HC2) to the preset operation mode of the multi-functional counter FB, the preset is disabled in the ...
When you use preset operation in the linear operation mode, counting is sometimes discontinued due to preset overflow.
Show Detail
- No:1675
- Displayed Date:2023/04/25 19:00
- Category:
Function
-
What is the rated current value of the fuse in the power supply module (NP1S-22)? I want to know to select the circuit breaker on the primary side ...
The rated current is 3 A.
Show Detail
- No:1641
- Displayed Date:2023/04/25 19:00
- Category:
Main unit
-
In a multi-CPU system, I set the 'Output reference input' of the I/O group registration but the variable (contact) specified for the output referen...
To enable the 'output value reference input,' the output module must be actually mounted. If the output module is set as 'unimplemented' in the system config...
Show Detail
- No:1637
- Displayed Date:2023/04/25 19:00
- Category:
Application