The total extension of the SX bus has exceeded 25 m. Is there anything to relay the connection?
The bus can be extended with the SX bus electrical repeater (Type_ NP2L-RP1). Up to three repeaters can be used in one system. (When three repeaters are us... Show Detail
Can I upload a definition file downloaded from a configurator to NP1L-PD1/PD2?
No, you cannot upload a definition file. So, it is very important to keep backup of Definition file on PC side. Show Detail
Please tell me how to register a T-link model of UG (or V Series) as a POD in the system definition.
Select a T-link capsule and set the numbers of input/output words. By default, a POD requires one word for input and one word for output. Show Detail
UI4 is not supported by the specification with the VB automation interface. Meanwhile, UI4 is supported by the custom interface specification. Show Detail
The base board that plays the role of a hub of optical converter modules is not represented in the system definitions. When the power supply (PS) of the sam... Show Detail
The Web module requires Java software only for trend graph display. The cause is probably that the PC you are using does not have Java installed. Show Detail
The flashing of the LED of the high-speed output module (Type_ NP1Y32T09P1-A) indicates that pulse output is generated. If no pulse output is generated in t... Show Detail
When the power supply recovers to normal, the ALM contact automatically returns to the original position (open). Show Detail
Only when the MICREX-F CPU is F55/F70/F70S/F80H/F120H/F120S to F150S, you can connect a MICREX-SX series T-link interface module although the order of the bi... Show Detail
The received data is cleared to 0. Therefore, be sure not to read (ignore) the data by application program. Reopening the FB (turning the 'OPEN' terminal fro... Show Detail