When the P-link module is specified as 'unimplemented' and no P-link module exists in the system, attempting to access the P-link memory using a contact, coi... Show Detail
The input/output data continue to be valid after the CPU is switched. (The previous values are retained.) Show Detail
It is not possible for the user to restore the factory setting. The module will have to be returned to the factory for initialization for a fee. Contact ou... Show Detail
Since the conversion accuracy after a scaling change remains within the specifications, rescaling is unnecessary. Show Detail
I don't have the SX bus loop-back plug (Type_ NP8B-BP). Can I use the SX bus cable instead?
You can use it provided that the system is a single-unit system (configured with one base only). Connect the connectors at both ends of the cable to IN and ... Show Detail
Which mode does the Ethernet module (Type_ NP1L-ET1/ET2) support, half or full?
Only the NP1L-ET1 supports both modes automatically (auto negotiation). Since the NP1L-ET2 is designed for 10Base5 (coaxial), it is fixed to half duplex. Show Detail
This problem was probably caused by the following factors_ (1) Failed contact of the connector on the SPH, (2) Failed contact on the POD (UG), (3) Improp... Show Detail
How does the FL-net module (Type_ NP1L-FL1/FL2/FL3) clear the error history recorded in each memory?
Once an error history is generated, it is retained internally within the FL-net module and is cleared when the power is turned off and turned on again or whe... Show Detail
You cannot use software filters when you use the pulse counter input function of the high-speed input module (Type_ NP1X3206-A). Show Detail
The rated current is 3 A. Show Detail